错误代码
型号
品牌
错误类型
错误原因
解决办法
1
MOVITRAC-31C
SEW
Overcurrent
Short circuit/earth fault at the output.Motor too large.Faulty
output stage.
Remove short-circuit.Connect smaller motor.If fault can still
not be reset,contact SEW service.
2
MOVITRAC-31C
SEW
DC link voltage
DC link voltage too high.
Increase deceleration ramps.
3
MOVITRAC-31C
SEW
Brake chopper
Regenerative power too highBraking resistor circuit
interruptedShort-circuit in the brakingresistor circuitBraking
resistance value too highFaulty brake chopper
Increase deceleration ramps.Check connecting leads of
thebraking resistor.Check technical data of thebraking
resistor.Exchange MOVITRAC® 31C
5
MOVITRAC-31C
SEW
Regenerativeoverload
With active regen. n monit. (P520/P522)and speed control
(P770):faulty encoder signalswrong number of pole pairs
(P324/P344)value of increments (P773) not correct
Check encoder.Check encoder connection.Set number of pole pairs
correctly.Set value of increments correctly.
4
MOVITRAC-31C
SEW
Cont. overload
´t utilization too high (> 125(%)).
Reduce load.
6
MOVITRAC-31C
SEW
Overtemperature
Thermal overload of the inverter.
Reduce load and / or ensure adequatecooling.
7
MOVITRAC-31C
SEW
Phase failure
With active mains volt. monitor.(P530)Phase missing at TL.
X1:1/2/3.
Check mains supply.
10
MOVITRAC-31C
SEW
Direction ofrotation
Only with active speed control (P770):Encoder tracks A/A and
B/B areswapped in pairs.Motor rotates in opposite direction.Regen.
overload (i.e. with sagging hoist)because of excessive load or
BOOSTsetting too low (P321/P341).
Check encoder connection.Exchanging two motor phases.Reduce
load or i