故障代码 故障现象/类型 故障原因 解决对策
1 Overcurrent Short circuit/earth fault at the output. Motor too large. Faulty output stage. Remove short-circuit. Connect smaller motor. If fault can still not be reset, contact SEW service.
2 DC link voltage DC link voltage too high. Increase deceleration ramps.
3 Brake chopper Regenerative power too high Braking resistor circuit interrupted Short-circuit in the braking resistor circuit Braking resistance value too high Faulty brake chopper Increase deceleration ramps. Check connecting leads of the braking resistor. Check technical data of the braking resistor. Exchange MOVITRAC® 31C
5 Regenerative overload With active regen. n monit. (P520/P522) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
4 Cont. overload ´t utilization too high (> 125(%)). Reduce load.
6 Overtemperature Thermal overload of the inverter. Reduce load and / or ensure adequate cooling.
7 Phase failure With active mains volt. monitor.(P530) Phase missing at TL. X1:1/2/3. Check mains supply.
10 Direction of rotation Only with active speed control (P770): Encoder tracks A/A and B/B are swapped in pairs. Motor rotates in opposite direction. Regen. overload (i.e. with sagging hoist) because of excessive load or BOOST setting too low (P321/P341). Check encoder connection. Exchanging two motor phases. Reduce load or increase BOOST.
11 Speed detection Only with active speed control (P770): Faulty encoder connection. FEN31C/FPI31C option not installed. Check encoder connection. Insert correct option (FEN31C or FPI31C).
12 Mot. overload With active n monit. (P510/P512) and speed control (P770): faulty encoder signals wrong number of pole pairs (P324/P344) value of increments (P773) not correct Check encoder. Check encoder connection. Set number of pole pairs correctly. Set value of increments correctly.
13 Starting conditions With active hoist function (P710/P712): Current too low during the premagnetization phase: Motor rated power selected too small in relation to the inverter rated power. Cross-section of the motor leads too small. Check startup data and carry out new startup if necessary. Check inverter-motor connection. Check cross-section of the motor leads and increase if necessary.
14 Output open With active hoist function (P710/P712): Two or all output phases interrupted. Motor rated power selected too small in relation to the inverter rated power. Check inverter-motor connection. Check startup data and carry out new startup if necessary.
17 Stack overflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
18 Stack underflow Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
19 NMI trap Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
20 Undefined opcode Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
21 Protected instr. Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
22 Word op. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.
23 nstruct. access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly,
24 Ext. bus access Inverter electronics faulty. Possible cause: EMC effect. The notes for EMC compliant installation must be observed. The reset for error 25 consists of several steps: 1. Factory setting (P830 = YES) 2. Re-set matched parameters 3. Carry out reset If fault occurs repeatedly, contact SEW service.