A new flat-plate heat pipe with vein structure grooves is proposed. Different fractal angle (50°, 60°, 70°, 80° and 90°) of the vein structure are examined. The size of the vein structure groove is decreasing along radial direction. Both the length and width ratio of the downstream groove to upstream groove is 0.7. The central groove has a length of 16.0mm, a width of 2.0mm, and a depth of 0.3mm. A comparison study of a flat-plate heat pipes without surface treatment is also made. The results show that the most optimal fractal angle of the vein structure is 80°. When the heat pipe has the smallest condensation thermal resistance of 39.42℃/KW, 40.29% lower than the untreated flat-plate heat pipe. Compared with traditional straight channel structure, the venous channel structure also greatly reduce flow resistance, which is conducive to the return of the working fluid.