wincc打不开项目 本地服务器不可用,打开提示启动本地服务器后,出现:cannot open wincc project。。。...

打开提示启动本地服务器后,出现:cannot open wincc project,project manager for configured server is not running

佳答案

1.打开Start -> Programs -> Microsoft SQL Server 200x->Configuration Tools ->SQL Server Configuration Server看看服务器有没有启动。

2.参考英文论坛的处理方法试试:

I resolved the isuse as follows:

1) Moved the Projekt to C:Documents and SettingsAll UsersDocumentsSiemensWinCCProjects————移动项目到C:Documents and SettingsAll UsersDocumentsSiemensWinCCProjects目录下。

2) Recursively removed the Read Only attrubutes (at some point the project was on a CD and this attribute wanders along untill explicitely removed.)

3) Recursively removed the "Compressed" property

参考资料:http://www.automation.siemens.com/WW/forum/guests/PostShow.aspx?PostID=202902&language=en

  • 1
    点赞
  • 4
    收藏
    觉得还不错? 一键收藏
  • 0
    评论

“相关推荐”对你有帮助么?

  • 非常没帮助
  • 没帮助
  • 一般
  • 有帮助
  • 非常有帮助
提交
评论
添加红包

请填写红包祝福语或标题

红包个数最小为10个

红包金额最低5元

当前余额3.43前往充值 >
需支付:10.00
成就一亿技术人!
领取后你会自动成为博主和红包主的粉丝 规则
hope_wisdom
发出的红包
实付
使用余额支付
点击重新获取
扫码支付
钱包余额 0

抵扣说明:

1.余额是钱包充值的虚拟货币,按照1:1的比例进行支付金额的抵扣。
2.余额无法直接购买下载,可以购买VIP、付费专栏及课程。

余额充值