启动wcc显示本地服务器失败,打开提示启动本地服务器后,出现:cannot open wincc project。。。...

打开提示启动本地服务器后,出现:cannot open wincc project,project manager for configured server is not running

最佳答案

1.打开Start -> Programs -> Microsoft SQL Server 200x->Configuration Tools ->SQL Server Configuration Server看看服务器有没有启动。

2.参考英文论坛的处理方法试试:

I resolved the isuse as follows:

1) Moved the Projekt to C:\Documents and Settings\All Users\Documents\Siemens\WinCCProjects————移动项目到C:\Documents and Settings\All Users\Documents\Siemens\WinCCProjects目录下。

2) Recursively removed the Read Only attrubutes (at some point the project was on a CD and this attribute wanders along untill explicitely removed.)

3) Recursively removed the "Compressed" property

http://www.automation.siemens.com/WW/forum/guests/PostShow.aspx?PostID=202902&language=en

参考资料:http://www.automation.siemens.com/WW/forum/guests/PostShow.aspx?PostID=202902&language=en

提问者对于答案的评价:

谢谢

原创文章,作者:more0621,如若转载,请注明出处:https://www.zhaoplc.com/plc265174.html