- 1200PLC本体自带有2路0-10V模拟量输入端口;
- 不支持4~20mA电流信号输入(需要外接电阻转换);
- 0~10V==>0~27648
通道接线:
通道组态:
工程量转换程序:ScaleWR
ScaleWR的源码:
IF #IN >#IN_High THEN
// Statement section IF
#OUT:=#OUT_High;
RETURN;
END_IF;
IF #IN<#IN_Low THEN
// Statement section IF
#OUT := #OUT_Low;
RETURN;
END_IF;
#OUT := (INT_TO_REAL((#IN-#IN_Low)))*(#OUT_High-#OUT_Low)/ (INT_TO_REAL((#IN_High-#IN_Low)))+#OUT_Low;
ScaleWR的调用: