- 收到了这个报警
2017-09-19T08:58:43+08:00 2017 SW-A-4 %%10DEV/1/FAN_DIRECTION_NOT_PREFERRED: -Slot=2; Fan 2 airflow direction is not preferred on slot 2, please check it.
- 检查
[SW-A-4]dis fan
Slot 1:
Fan 1:
State : Normal
Airflow Direction: Port-to-power
Prefer Airflow Direction: Port-to-power
Fan 2:
State : Normal
Airflow Direction: Port-to-power
Prefer Airflow Direction: Port-to-power
Slot 2:
Fan 1:
State : FanDirectionFault
Airflow Direction: Port-to-power
Prefer Airflow Direction: Power-to-port
Fan 2:
State : FanDirectionFault
Airflow Direction: Port-to-power
Prefer Airflow Direction: Power-to-port
```
* 优化调整
[SW-A-4]fan prefer-direction slot 2 port-to-power
* 效果查看
[SW-A-4]dis fan
Slot 1:
Fan 1:
State : Normal
Airflow Direction: Port-to-power
Prefer Airflow Direction: Port-to-power
Fan 2:
State : Normal
Airflow Direction: Port-to-power
Prefer Airflow Direction: Port-to-power
Slot 2:
Fan 1:
State : Normal
Airflow Direction: Port-to-power
Prefer Airflow Direction: Port-to-power
Fan 2:
State : Normal
Airflow Direction: Port-to-power
Prefer Airflow Direction: Port-to-power
“`