04240FD11234A 特征
支持具有I/O 总线功能版本 16 及更高版本的紧凑型登录处理器(不支持 MicroLogix 1500)
附加指令创建 UDT,为 I/O、状态和控制数据提供逻辑定义
模块配置备份在压缩日志项目(ACD 文件)
模块充当协处理器,减少对 PLC 扫描时间的影响
支持多达 240 字的 I/O 数据
处理器控制器标签中提供诊断数据,可根据节点运行状况做出决策
附加配置文件支持,改进了在 CompactLogix 系统中的集成
应用程序端口可配置为模块总线主站或模块总线从站
作为模块总线主站,支持多达 30 个模块总线命令
最适合 OEM 和机器制造商应用
支持安然和丹尼尔风格的浮点数据实现
Function description
The GE Ethernet/IONet switch ESWB has five versions (H1A to H5A), which differ in the types of optical ports they can contain, such as none, multi-mode, or single-mode (long-distance) ports.
Depending on the hardware form (ESWA or ESWB) and the DIN rail mounting direction selected, the ESWx switch can be mounted to the DIN rail using one of three GE certified DIN rail mounting clips. The following table outlines the individual order of clips. Each switch has mounting screws.
Input voltage dips (also known as power failures) may cause the ESWB I/O network (IONet) switch to restart incorrectly and, in some cases, fail to re-establish communication with the system. If the ESWB switch encounters power failure and the input 28 V line drops below the minimum operating voltage, but not completely to 0 V, the switch may not restart correctly when the input voltage recovers above the minimum operating voltage.
If this happens, the ESWB LED will remain stable, flash synchronously, or scroll from side to side, and the switch will not reconnect. If the site encounters power failure, please check the LED in front of the switch after the voltage returns and IONet loses communication. If they are stable, flashing synchronously, or scrolling, manually restart the switch by restarting the power.