TwinCAT3 Error starting TwinCAT system! 报错问题

TwinCAT3 Error starting TwinCAT system! 报错问题

Win10系统下 TwinCAT3 首次使用运行项目时会出现如图报错:

'TwinCAT System' (10000): Sending
ams command >> lnit4\RTime: Start Interrupt: Ticker started >>
AdsError: 4115 (0x1013, RTIME: system clock setup fails.
Hint: On Windows8 system and above execute win8settick.bat in
TwinCAT\3.1\System as administrator and reboot.) << failed!
Error starting TwinCAT system!
lnit4\RTime: Start Interrupt: Ticker started >> AdsError: 4115 (0x1013,
RTIME: system clock setup fails.
Hint: On WindowsS system and above execute win8settick.bat in
TwinCAT\3.1 \System as administrator and reboot.)
For further information start the event viewer and open the application
log.

在这里插入图片描述

解决方法

在C:\TwinCAT\3.1\System路径下找到win8settick.bat文件并执行,然后重启电脑。