DSDX 452
DSDX 452L
DSDX 454
DSDX 454L
DSDI 452
DSDI 454
用于20个24 V数字输入和12个数字输出的组合单元。这些输入具有与DSDI 452上的输入相同的质量。输出是完全分离的继电器触点,适用于24 V-240 V a.c.直流电。触点上的建议最小负载为2.5 VA,但适用于24伏直流电时最小负载为100 mA。带有附加字母L的装置配有低压继电器触点。触点上的最大负载为200 mA。建议触点上的最小负载为5 mA或0.05 VA。
用于20个数字输入(48 V)和12个数字输出的组合单元。这些输入具有与DSDI 454上的输入相同的质量。输出是完全分离的继电器触点,适用于24 V-240 V a.c.直流电。触点上的建议最小负载为2.5 VA,但适用于24伏直流电时最小负载为100 mA。带有附加字母L的装置配有低压继电器触点。触点上的最大负载为200 mA。建议触点上的最小负载为5 mA或0.05 VA。
DCS grounding classification
In general, DCS control systems require two types of grounding: protective grounding and working grounding (logical grounding, shielding grounding, etc.). For systems equipped with safety barriers and explosion-proof measures, such as those used in the chemical industry, intrinsic safety measures are also required.
(1) Cabinet Grounding (CG) is a protective measure taken to prevent the accumulation of static charges in the equipment casing and avoid personal injury. All operator cabinets, on-site control station cabinets, printers, terminal cabinets, etc. of the DCS system should be grounded for protection. The protective ground should be connected to the electrical professional grounding network in the factory area, with a grounding resistance of less than 4 Ω.
(2) Logically: also known as machine logic ground or host power ground, it is the common ground of the negative end of the logic level inside the computer and also the output ground of the+5V power supply. For example, the positive and negative 5V and positive and negative 12V terminals of the CPU. Need to connect to a public grounding electrode.
(3) Analog grounding (AG), also known as analog grounding, can shield the interference received during on-site signal transmission to improve signal accuracy. The shielding layer of signal cables in the DCS system should be grounded through shielding. The cable shielding layer must be grounded at one end to prevent the formation of closed circuit interference. The metal armor of armored cables should not be grounded as shielding protection, but must be grounded with copper wire mesh or aluminum shielding layer. Connect to the public grounding electrode.
(4) Intrinsically safe grounding should have an independent grounding system with a grounding resistance of ≤ 4 Ω. The grounding system of intrinsically safe grounding should remain independent, and the distance from the electrical grounding network or other instrument system grounding network in the factory area should be at least 5m.