每个板/单元/模块通常由aGDWDEDVHHOHPHHW表示。这同样适用于板/单元/模块的各个通道。对于S100 I/O中的数字输入板,有一个高级DI板元件和32个数字输入(通道)元件。对于S400 I/O单元或S800 I/O模块,存在定义该单元(AX单元、DX单元)或模块的相应上级元素。比较不同的I/O系统S100 I/O、S400 I/O和S800 I/O,各个通道元件几乎相同。上级元素由用户/配置器创建。因此,相关的各个频道元素会自动出现。下面列出的一些板类型有一个或多个3&HOHPHQWVa应用程序接口。

DCS system grounding method
(1) Utilize the electrical grounding grid as the DCS grounding grid, i.e. share grounding with the electrical grounding grid;
(2) Establish a dedicated and independent grounding network for the DCS system;
(3) Establish a dedicated grounding network for DCS, which is connected to the electrical grounding network through a grounding wire;


Due to the many similarities between the third grounding method and the second grounding method, in the past, computer or DCS systems have often used dedicated grounding grids. However, the drawbacks of this grounding method are: large land area, high investment, high consumption of cables and grounding network steel, considerable distance from the factory building (as it is difficult to find a suitable location within the factory building), inconvenient management, maintenance, measurement, and searching for grounding electrodes and wires, and poor effectiveness.

According to actual operation, setting up a dedicated DCS grounding network is both difficult and unsafe. For example, a certain power plant has experienced dozens of unit trips due to grounding issues. According to the investigation, many power plant DCS later switched to electrical grounding grids for grounding, achieving good results.