DCS system grounding method
(1) Utilize the electrical grounding grid as the DCS grounding grid, i.e. share grounding with the electrical grounding grid;
(2) Establish a dedicated and independent grounding network for the DCS system;
(3) Establish a dedicated grounding network for DCS, which is connected to the electrical grounding network through a grounding wire;
Due to the many similarities between the third grounding method and the second grounding method, in the past, computer or DCS systems have often used dedicated grounding grids. However, the drawbacks of this grounding method are: large land area, high investment, high consumption of cables and grounding network steel, considerable distance from the factory building (as it is difficult to find a suitable location within the factory building), inconvenient management, maintenance, measurement, and searching for grounding electrodes and wires, and poor effectiveness.
According to actual operation, setting up a dedicated DCS grounding network is both difficult and unsafe. For example, a certain power plant has experienced dozens of unit trips due to grounding issues. According to the investigation, many power plant DCS later switched to electrical grounding grids for grounding, achieving good results.